Omnicare EVC Cabling & Networking
The Omnicare EVC system is loop wired – with any combination of outstations on a single loop. Omnicare has full
networking capability.</
disabled toilet alarms to be connected to one master control panel. (You may like to know that we have BIM drawings for the Omnicare system. If you
would like copies of these please click on the link at the bottom of this page.)
- There are two main components – the master control panel(s) and
the remote units (disabled refuge, fire telephone, steward telephone, combined outstation and disabled toilet alarm) - Remote units are wired in a ring circuit configuration and are ‘self-
learning’, with an auto-commissioning feature - Fire rated enhanced four core cable with a screen must be used for
loops in a system used for fire fighting. Standard fire resisting cables
could be considered suitable for some EVC systems (please refer to
leaflet or BS5839-9 for more details). - Door latch initiates call
- Any combination of remote units can be linked to the control panel
on a single wiring loop - Up to 200m cable run between remote units and master control
panel as standard. A repeater unit (BVOCRIF) must be used if
distance between remotes exceeds 200m - Typically 20-30 remotes per loop
- Repeater units (BVOCRIF) are used to connect the DTAKIT 3-part
toilet alarm to the system
Like to discuss a project?
Call us on 08005003013
TO BOOK A VISIT FOR OMNICARE CABLING & NETWORKING
or for a quote and site analysis for a new installation please call on
08005003013. Or fill out the quick contact form below.